Standard Single-Duct VAV for Commercial Offices
Base YFVAV-S-T100 configuration for interior zones requiring pressure-independent primary cooling modulation. Controls airflow directly in response to zone temperature sensors.
A VAV terminal must hold zone airflow across changing duct pressure while staying inside the required minimum, maximum, acoustic and reheat limits.
YONGFAN’s YFVAV-S-T100 Single-Duct VAV Terminal Family covers nine precision inlet sizes from Ø125 to Ø400 mm spanning 122 to 6,232 m³/h. Features multi-point cross-averaging airflow sensing, pressure-independent DDC actuator integration, optional 1-row/2-row hot-water reheat coils (1.6–34.6 kW), and 914 mm acoustic attenuator sections.
A pressure-dependent terminal moves its damper based on thermostat demand alone; if upstream duct pressure shifts, actual delivered airflow changes even though the damper position hasn’t moved.
A pressure-independent terminal measures actual airflow through an integrated multi-point sensor and dynamically readjusts damper position to maintain the commanded volume regardless of static pressure swings in the supply duct.
Oversizing leads to unstable minimum-flow control at the bottom of the sensor range, while undersizing creates excessive inlet pressure drop and acoustic breakout noise.
ASHRAE Handbook — Air Handling and Distribution defines pressure-independent VAV operation: the room thermostat resets the required airflow setpoint between scheduled minimum and maximum limits, while the terminal independently maintains measured flow.
Integrated flow sensor and actuator loop holds CFM setpoints constant regardless of upstream main duct pressure fluctuations.
Aerodynamic internal blade and flow sensor profile achieves minimal pressure loss as low as 2 Pa at wide-open design flow.
1-row (1.6–17.5 kW) or 2-row (2.7–34.6 kW) hot-water coils provide sensible perimeter heating during minimum ventilation flow.
| Model Code | Minimum Airflow | Maximum Airflow | Inlet Diameter | Box Dimensions (Z × X × Y) |
|---|---|---|---|---|
YFVAV-S-T100-05 |
122 m³/h | 612 m³/h | Ø125 mm |
400 × 270 × 280 mm |
YFVAV-S-T100-06 |
176 m³/h | 880 m³/h | Ø150 mm |
400 × 270 × 280 mm |
YFVAV-S-T100-07 |
238 m³/h | 1,190 m³/h | Ø175 mm |
400 × 320 × 280 mm |
YFVAV-S-T100-08 |
312 m³/h | 1,560 m³/h | Ø200 mm |
400 × 320 × 280 mm |
YFVAV-S-T100-09 |
394 m³/h | 1,972 m³/h | Ø225 mm |
400 × 370 × 330 mm |
YFVAV-S-T100-10 |
486 m³/h | 2,430 m³/h | Ø250 mm |
400 × 370 × 330 mm |
YFVAV-S-T100-12 |
700 m³/h | 3,500 m³/h | Ø300 mm |
450 × 420 × 380 mm |
YFVAV-S-T100-14 |
952 m³/h | 4,760 m³/h | Ø350 mm |
500 × 470 × 430 mm |
YFVAV-S-T100-16 |
1,246 m³/h | 6,232 m³/h | Ø400 mm |
500 × 520 × 480 mm |
Base YFVAV-S-T100 configuration for interior zones requiring pressure-independent primary cooling modulation. Controls airflow directly in response to zone temperature sensors.
Incorporates an integrated 914 mm lined acoustic silencer section downstream of the damper assembly to eliminate regenerated air noise and duct-borne sound.
Equipped with a factory-installed 1-row or 2-row copper-tube aluminum-fin hot-water coil. Modulates primary cool air for ventilation while heating water coil satisfies perimeter envelope transmission losses.
Attaches to the terminal discharge to divide air directly among multiple ceiling swirl, slot or square diffusers via flexible ducting, eliminating complex branch sheet metal ductwork.
Submitting your minimum and maximum airflow schedule, available inlet static pressure, acoustic target, reheat parameters, and BMS protocol enables our engineers to provide complete submittal schedules.
Fabricated using precision CNC punch presses, automated folding lines, and dedicated coil tube-expanding, fin-pressing, and brazing machinery.
Reheat coils receive 100% pneumatic pressure leak testing; completed VAV boxes are tested for airflow sensor calibration and mechanical operation before crating.
Each terminal is tagged with a unique serial identifier linking factory calibration curves, actuator configurations, and inspection records.
Do not use one terminal to serve spaces requiring independent temperature setpoints just because a multi-outlet plenum can feed multiple rooms.
Do not simply select the smallest inlet that can hit maximum airflow if the resulting velocity creates excessive acoustic noise or pressure drop.
For airflow demands exceeding the 6,232 m³/h round-duct limit, transition to the high-capacity YF-VTT series rather than extrapolating S-T100.
The YFVAV-S-T100 measures airflow and adjusts its damper so the commanded zone airflow is maintained as upstream duct pressure changes within the usable operating range.
Across all nine documented sizes, the family covers 122–6,232 m³/h (approx. 72–3,668 CFM).
The documented round inlets run from Ø125 to Ø400 mm across models -05 through -16.
Several YFVAV-S-T100 sizes overlap around that airflow (e.g. -08, -09, -10). Select from minimum and maximum flow, inlet velocity, available static pressure, acoustic requirement and ceiling space.
Yes. YONGFAN offers 1-row or 2-row hot-water reheat coils. Indicative family heating capacities are approximately 1.6–17.5 kW and 2.7–34.6 kW, respectively.
Yes. The supplier documents a 914 mm lined attenuator section for noise-sensitive hotel guest rooms and executive spaces.
Yes. Pair the YFVAV-S-T100 with the YF-MOA Multi-Outlet Distribution Plenum where several diffusers belong to the same control zone.
The supplier source supports Modbus / BACnet integration. Confirm the controller and required points list for the ordered configuration.
Connect minimum and maximum airflow, inlet diameter, pressure drop, acoustics, reheat duty, and BMS protocol into one confirmed terminal schedule. Send your zone schedule to our application engineers.