Life Safety & Smoke Control · 280 °C / 30 min Fans · FHF 70 °C & PFHF 280 °C Dampers · PYF DC24V Valves

Fire & Smoke Exhaust Systems: Coordinated Emergency Sequence of Operation

Fire and smoke control is a sequence problem before it is an equipment problem. The fan, damper, actuator, duct path and control signal must all move to the correct state at the correct point in the fire event.

Coordinate YONGFAN HTFC fire smoke-exhaust fan boxes (280 °C / 30 min, single/dual speed 1,400–171,000 m³/h), DTF in-line axial smoke fans, PYHL-14A jet-induction exhaust, FHF 70 °C fire isolation dampers, PFHF 280 °C smoke-exhaust fire dampers, PYF normally closed DC24V smoke valves, and 3C fire actuators.

FHF Fire Damper Normally Open · 70 °C Close
PFHF Smoke Damper Normally Open · 280 °C Close
PYF Smoke Valve Normally Closed · DC24V Open
HTFC Smoke Fans 280 °C / 30 min · Dual Speed
Fire-rated smoke exhaust fan box and motorized fire dampers in commercial building mechanical shaft
Life-Safety Smoke Control HTFC 280 °C Fans · DTF Axial · FHF 70 °C Isolation · PFHF 280 °C Extract · PYF DC24V Valves
01 / Life Safety Sequence Analysis

The Wrong Damper Sequence Can Defeat The Correct Fan

A smoke-exhaust fan starts, but the extract damper remains closed without feedback; or a 70 °C fire damper closes prematurely in a dedicated smoke path, blocking smoke extraction.
Fire smoke damper actuator wiring, position feedback microswitches and thermal fusible links
Coordinated Fire Cause-and-Effect Matrix

FHF (70 °C Isolation) · PFHF (280 °C Extract Shutdown) · PYF (DC24V Signal Open)

Normal ventilation paths isolate at 70 °C; dedicated smoke extract paths open via PYF on fire signal; PFHF remains open during smoke evacuation until 280 °C high-temp cutoff.

Premature 70 °C Damper Closure in Smoke Path

Installing a standard 70 °C FHF fire damper in a dedicated smoke exhaust duct closes the extraction route early during a fire event.

Impact: Trapped toxic smoke & blocked evacuation corridors

Missing Position Feedback Interlock

Starting high-power smoke exhaust fans before PYF smoke valves confirm open position creates severe duct implosion shock.

Impact: Collapsed ductwork & tripped smoke fan motors

Single-Speed Fan Oversizing

Using oversized single-speed smoke fans for everyday low-speed ventilation wastes electrical energy and creates acoustic complaints.

Impact: High operating energy costs & continuous noise

Unapproved Silencers in High-Temp Ducts

Installing standard acoustic silencers with combustible internal packing inside high-temperature smoke-control ductwork.

Impact: Fire hazard & smoke generation inside the attenuator

The Four Pillars of Smoke & Fire Coordination

Isolate non-fire compartments, open smoke paths, operate high-temp fans, and signal position proof.

01 / FHF Fire Dampers Normally open; operates at 70 °C to cut off HVAC fire-compartment penetrations
02 / PFHF Smoke Dampers Normally open in smoke ducts; stays open during smoke exhaust, shuts at 280 °C
03 / PYF Smoke Valves Normally closed; opens upon DC24V fire command to establish extraction path
04 / HTFC & DTF Fans 280 °C / 30 min rated; HTFC-II dual speed serves normal ventilation + fire exhaust
02 / Portfolio Showcase

Fire & Smoke Control Product Families

Detailed engineering review of YONGFAN’s fire dampers, smoke valves, actuators, and fire-rated fans.
01 · FHF Dampers Fire Compartment Isolation · 70 °C Fusible

FHF Fire Dampers (WS-FK, WSDc-FK, WSDj-FK)

Normally open fire dampers installed at fire-partition walls and floor slabs. Cuts off airflow and smoke migration when duct temperature reaches 70 °C. WS-FK features manual reset & 5-position adjustment; WSDc-FK adds DC24V electric closing; WSDj-FK adds motorized DC24V reset.

Normal Position
Normally OPEN during Standard HVAC
Thermal Trigger
70 °C Fusible Link Automatic Close
Electric Command
DC24V Solenoid Trigger (WSDc/WSDj)
Reset Options
Manual Reset or DC24V Motorized Reset (WSDj)
Primary Applications

HVAC duct penetrations through firewalls, floor slabs, and compartment boundary partitions.

02 · PFHF Dampers Smoke Path High-Temp Cutoff · 280 °C Fusible

PFHF Smoke-Exhaust Fire Dampers (WS-K, WSDc-K, WSDj-K)

Normally open damper installed directly in dedicated smoke-exhaust ducts. Remains open during smoke extraction, allowing hot smoke to be evacuated. Closes automatically when smoke reaches 280 °C to isolate the path and protect downstream exhaust fans and shafts.

Normal Position
Normally OPEN in Smoke Extract Path
Thermal Trigger
280 °C High-Temp Fusible Element Close
Electric Options
WSDc-K (DC24V Close) & WSDj-K (Motorized Reset)
Signal Output
Closed-Position Microswitch Feedback
Primary Applications

Mechanical smoke-exhaust duct branches, smoke shaft junctions, and fan inlet protection headers.

03 · PYF Valves Smoke Extract Opening · Normally Closed · DC24V

PYF Smoke-Exhaust Valves (SDc-K, SDj-K, SDc-YK-BS)

Normally closed smoke valves installed at smoke extraction points and wall outlets. Opens on a DC24V command from the fire alarm system to create the smoke evacuation path. Includes SDc-K standard electric, SDj-K motorized reset, SDc-YK remote reset, and SDc-YK-BS panel smoke outlets.

Normal Position
Normally CLOSED during Standard HVAC
Trigger Action
DC24V Fire Command OPENS Valve
Position Feedback
Open-Position Microswitch Signal Output
Panel Variant
SDc-YK-BS Decorative Wall/Ceiling Panel
Primary Applications

Smoke evacuation points in public corridors, shopping mall atriums, and underground car park smoke zones.

04 · HTFC Fan Boxes Centrifugal Fire Smoke Fan Box · 280 °C / 30 min

HTFC Fire Smoke-Exhaust Fan Boxes

Double-inlet centrifugal fan box with external motor, rated for 280 °C / 30 min smoke duty (1,400–171,000 m³/h, 190–1,460 Pa, 56–106 dB(A)). HTFC-I provides dedicated single-speed smoke exhaust; HTFC-II provides dual-speed operation (low speed for daily ventilation, high speed for fire smoke exhaust).

Fire Rating
280 °C for 30 Minutes Smoke Duty
Airflow Range
1,400 to 171,000 m³/h
Total Pressure
190 to 1,460 Pa
HTFC-II Dual Speed
Low Speed (Ventilation) / High Speed (Smoke)
Primary Applications

Commercial building smoke exhaust plant rooms, rooftop smoke extraction, and dual-purpose parking ventilation.

05 · DTF Axial Fans In-Line Axial Smoke Fan · 280 °C / 30 min

DTF Series Axial-Flow Tube Exhaust Fans

In-line tube-axial fan engineered for direct duct mounting with documented 280 °C / 30 min fire smoke exhaust rating (1,886–114,829 m³/h, 115–2,266 Pa, Ø350–1600 mm, 0.5–45 kW). Provides compact straight-through airflow without large cabinet footprints.

Airflow Capacity
1,886 to 114,829 m³/h
Total Pressure
115 to 2,266 Pa High Pressure
Fire Rating
280 °C for 30 Minutes Certified Build
Impeller Sizes
Ø350 to Ø1,600 mm Diameter
Primary Applications

Direct in-line vertical/horizontal smoke shafts, tunnel ventilation shafts, and metro station exhaust.

06 · PYHL-14A Underground Mixed-Flow Induction · 280 °C / 30 min

PYHL-14A Jet-Induction Fire Exhaust Fans

Mixed-flow jet-induction fan documented with 280 °C / 30 min fire rating for ductless underground car park and tunnel smoke extraction. Induces high-velocity momentum to sweep smoke toward dedicated smoke shafts without complex duct networks.

Application
Ductless Jet Induction Smoke Evacuation
Fire Duty
280 °C / 30 min Smoke Extraction
Airflow Envelope
Combined Range to 105,988 m³/h
Mounting
Ceiling-Suspended Directional Induction
Primary Applications

Underground car parks, loading docks, basement logistics hubs, and vehicular tunnels.

07 · 3C Actuators Fire-Rated Damper Actuators · DC24V

3C Fire-Rated Actuator Assemblies

Actuator assemblies certified to 3C / GB 15930-2007 standards for FHF, PFHF, and PYF dampers. Operating on DC 24 V (<0.7 A working current), providing integrated 70 °C / 280 °C sensor interfaces, position feedback microswitches, and manual or electric reset.

Rated Voltage
DC 24 V Operating Voltage
Working Current
<0.7 A Low Power Draw
Thermal Sensors
70 °C (FHF) / 280 °C (PFHF)
Position Feedback
Integrated SPDT Microswitch Contacts
Primary Applications

Direct mounting on FHF fire dampers, PFHF smoke dampers, and PYF smoke exhaust valves.

03 / Selection Routing

Fire & Smoke Damper Sequence Matrix

Compare FHF, PFHF, PYF, and fire fans by normal state, primary fire action, trigger condition, and system role.
DeviceNormal PositionPrimary Fire ActionDocumented TriggerTypical System Role
FHF Fire DamperNormally OPENCloses to isolate HVAC duct70 °C fusible link / DC24V closeFire-compartment boundary isolation
PFHF Smoke DamperNormally OPENStays open in smoke path, closes at high temp280 °C fusible link / DC24V closeHigh-temp shutdown in smoke-exhaust duct
PYF Smoke ValveNormally CLOSEDOpens to create smoke-exhaust pathDC24V fire-control signalSmoke outlet / extract-path opening
HTFC Fan BoxStandby / Low SpeedStarts / ramps to high speed for smoke extractFire alarm interlock / 280 °C / 30 minCentrifugal smoke extraction & daily ventilation
DTF Axial FanStandby / NormalStarts emergency smoke exhaustFire alarm command / 280 °C / 30 minIn-line vertical/horizontal shaft smoke exhaust
PYHL-14A FanStandby / NormalSweeps smoke toward extract shaftsFire alarm command / 280 °C / 30 minDuctless underground car park smoke induction
04 / Procurement Protocol

Information Required for Fire & Smoke System Sizing

Provide smoke zone dimensions, required smoke-exhaust airflow, fire-mode static pressure, damper sizes, and control voltages.
STEP 01

Smoke Zone & Flow

Identify smoke zones, required emergency airflow (m³/h), and applicable fire design standard.

STEP 02

Damper Schedule

List FHF (70 °C), PFHF (280 °C), and PYF (DC24V) locations, rectangular W×H or circular ØD sizes.

STEP 03

Fan Fire Duty

Select HTFC-I/II or DTF fans rated for 280 °C / 30 min with fire-mode external static pressure.

STEP 04

Cause & Effect

Define fire alarm interlocks, position feedback verification, and manual/electric reset logic.

Engineering Handoff

Submit Fire & Smoke Schedules for Engineering Verification

YONGFAN life-safety engineers will verify high-temperature fan performance points, check actuator power draw, match damper dimensions, and supply 3C / GB 15930 certificates.

Smoke Zone Area (m²) & Required Airflow (m³/h)
Fire-Mode External Static Pressure (ESP in Pa)
HTFC-II High/Low Speed Duty Points if dual-purpose
FHF (70 °C), PFHF (280 °C) & PYF Damper Schedule
Actuator Control Voltage: DC 24 V Standard
Required Fire Standards & Certification Documents
05 / Manufacturing QA

National Fire Testing & GB 15930 / JB/T 10281 Compliance

Fans and dampers undergo 280 °C high-temperature fire testing, mechanical endurance checks, and air tightness verification.
High-Temp QA

280 °C / 30 min Fire Testing

HTFC and DTF fire-rated fans are tested at national fire inspection centers for continuous operation at 280 °C for 30 minutes.

Damper QA

GB 15930-2007 Standards

FHF, PFHF, and PYF dampers are certified to GB 15930-2007 for blade closing reliability, leakage, and thermal release.

Actuator QA

3C Fire Actuator Testing

DC24V actuators undergo full stroke endurance testing, thermal sensor verification, and feedback microswitch checks.

Fan Run QA

JB/T 10281-2014 Verification

Centrifugal smoke fan boxes are verified for aerodynamic performance, impeller balance, and motor temperature rise.

Standard Fire Dampers: FHF, PFHF, and PYF dampers fabricated to W×H sizes in 10–15 working days. Fire Fan Boxes: HTFC-I/II and DTF fire smoke-exhaust fans dispatched with complete test reports.
06 / Engineering Knowledge

Fire & Smoke Exhaust Systems FAQ

Direct engineering answers regarding FHF vs PFHF, PYF valves, HTFC dual-speed operation, and actuators.

What is the difference between FHF and PFHF?

Both are normally open, but temperature action is different: FHF closes at 70 °C to isolate fire compartments; PFHF closes at 280 °C to protect smoke fans after smoke extraction.

What is PYF used for?

PYF is a normally closed smoke-exhaust valve. It opens upon receiving a DC24V fire command to establish the smoke evacuation path and sends position feedback.

Why is PFHF not set to 70 °C like FHF?

PFHF must remain open during smoke extraction so hot smoke (often 100–200 °C) can be safely evacuated without tripping the duct closed prematurely.

What is the HTFC fire duty?

Documented HTFC fire-smoke configurations are certified for 280 °C for 30 minutes continuous operation under fire conditions.

What is the difference between HTFC-I and HTFC-II?

HTFC-I is single-speed for dedicated smoke duty. HTFC-II is dual-speed (low speed for daily ventilation, high speed for emergency smoke exhaust).

Can DTF axial fans be used for smoke exhaust?

Yes. YONGFAN documents fire-rated DTF builds certified for 280 °C / 30 min smoke-exhaust duty in straight in-line ducts.

Are FHF, PFHF and PYF actuators 24 V?

Yes. Documented YONGFAN 3C fire-rated actuators operate on DC 24 V with <0.7 A working current and include feedback switches.

Does every smoke valve use a thermal fusible link?

No. The PYF smoke-exhaust valve does not use a fusible thermal link; its primary defining action is opening on the DC24V electrical fire command.

Should the smoke fan start before the damper opens?

No. Best practice requires the PYF smoke valve to return an open-position feedback signal before the smoke fan starts to prevent duct implosion.

Can an ordinary silencer be installed in a smoke-exhaust duct?

Only if the silencer construction is certified for high-temperature smoke service without combustible packing, and its pressure drop is included in the fan ESP calculation.

07 / Application Boundaries

Fire & Smoke Exhaust Engineering Boundaries

Key operational boundaries to respect when designing life-safety fire and smoke systems.
Boundary 01 / Damper Misuse

Do Not Merge FHF & PFHF

Never install a 70 °C FHF fire damper in a smoke-exhaust path, and never omit 70 °C FHF isolation at compartment walls.

Boundary 02 / Fire vs Standard

Verify 280 °C Certification

Standard comfort ventilation fans do not inherit 280 °C / 30 min ratings; ensure the exact ordered model code is fire-certified.

Boundary 03 / Cause & Effect

Project-Specific Logic

Example fire cause-and-effect sequences are illustrative; the project fire engineer and local jurisdictional fire code govern final logic.

Boundary 04 / Silencer Resistance

High-Temp Silencer Rules

Standard acoustic silencers must not be used in smoke ducts unless approved by fire authorities; include silencer pressure drop in fan sizing.

08 / Engineering Handoff

Plan Your Fire & Smoke Exhaust System

Send your smoke zone schedules, airflow rates, duct layout, and cause-and-effect matrix. YONGFAN life-safety engineers will verify high-temp fan curves, size dampers, and supply certified 3C submittal packages.

HTFC Fire Smoke Fan Boxes (280 °C / 30 min)HTFC-II Dual-Speed (Ventilation + Smoke)DTF In-Line Axial Smoke Fans (Ø350–Ø1600 mm)FHF Fire Dampers (Normally Open, 70 °C Fusible)PFHF Smoke Dampers (Normally Open, 280 °C Fusible)PYF Smoke Valves (Normally Closed, DC24V Open)3C Fire-Rated DC24V Actuator AssembliesPYHL-14A Car Park Smoke Induction Fans
YONGFAN life safety engineers reviewing smoke control schematics and fire damper cause and effect schedules
Direct Life-Safety Engineering Handoff
280 °C / 30 min fan curve verification, damper dimensioning & 3C certificate submittals.